Tittel: High current arc erosion on copper electrodes in air
Forfattere: Øyvang, Thomas
Fjeld, Elin
Rondeel, Wilhelm
Hagen, Svein Thore
Dato: 2011
Forlagets versjon: http://dx.doi.org/10.1109/HOLM.2011.6034779
Sammendrag: An arc fault inside metal enclosed switchgear will cause the pressure to rise and vaporization of electrode material may contribute to the pressure rise. An experimental study of high current arc erosion on copper electrodes in air has been performed, with an evaluation of fraction lost by gross melting and vaporization. All experiments were performed at NEFI High Voltage Laboratory in Skien, Norway. The measured mass loss from vaporization in our experiments seems to be negligible compared to erosion by gross melting.
Emneord: Moving arc
Copper
melting
Vaporization
Forlag: IEEE Press
Dokumenttype: Conference object
URI: http://hdl.handle.net/2282/1203
ISBN: 978-1-61284-648-4
Vises i samlingene:Institutt for prosess-, energi- og miljøteknologi
Institutt for elektro, IT og kybernetikk

Denne innførselen er lisensiert under en brukslisens. Alle innførsler i TEORA er beskyttet av opphavsrett.

 

TEORA bygger på DSpace 1.4
Høgskolen i Telemark har alle rettigheter til denne siden
Høgskolen i Telemark, Biblioteket, Postboks 203, 3901 Porsgrunn
Telefon: 35952543, E-post: teora@hit.no
Webmaster: Arild Skalmeraas
Teknisk ansvarlig: Rune Pettersen
Ansvarlig redaktør: Biblioteksjef Frode Bakken