Title: High current arc erosion on copper electrodes in air
Authors: Øyvang, Thomas
Fjeld, Elin
Rondeel, Wilhelm
Hagen, Svein Thore
Issue Date: 2011
Publishers version: http://dx.doi.org/10.1109/HOLM.2011.6034779
Abstract: An arc fault inside metal enclosed switchgear will cause the pressure to rise and vaporization of electrode material may contribute to the pressure rise. An experimental study of high current arc erosion on copper electrodes in air has been performed, with an evaluation of fraction lost by gross melting and vaporization. All experiments were performed at NEFI High Voltage Laboratory in Skien, Norway. The measured mass loss from vaporization in our experiments seems to be negligible compared to erosion by gross melting.
Keywords: Moving arc
Copper
melting
Vaporization
Publisher: IEEE Press
Document type: Conference object
URI: http://hdl.handle.net/2282/1203
ISBN: 978-1-61284-648-4
Appears in Collections:Institutt for prosess-, energi- og miljøteknologi
Institutt for elektro, IT og kybernetikk

This item is protected by a usage licens. All items in TEORA are protected by copyright.

 

TEORA runs on DSpace 1.4
Telemark University College owns all rights for this page
Telemark University College, Library, Postboks 203, 3901 Porsgrunn
Telephone: 35952543, Email: teora@hit.no
Webmaster: Arild Skalmeraas
Technical webmaster: Rune Pettersen
Editor: Biblioteksjef Frode Bakken